NYC Sprinkler System Inspection

In need of a NYC sprinkler system inspection? The professionals at Allstate Sprinkler Corp. are on the job. For over 40 years, We have built a reputation on the sound principle of providing professional service and high quality products to all our customers. Allstate Sprinkler Corp. is recognized as the one of the most responsive, thorough and reliable fire suppression contractors in NYC.

NFPA 25 Inspection

NFPA 25 requires an internal inspection of fire sprinkler system piping in NYC every five years. This is to be conducted to inspect for the “presence of foreign organic and inorganic material.” Foreign materials can cause obstructions to pipe and sprinklers.

Three levels of inspection

Internal Pipe Inspection

This requires the opening of a flushing connection at the end of one main and removal of one sprinkler head near the end of a branch line. These openings are to be inspected for the “presence of foreign organic and inorganic material.”

Internal Pipe Examination

For ‘at-risk’ systems, NFPA 25 lists conditions in which this type of internal pipe exam is to be performed. This inspection requires internal pipe examinations at the following four points of a fire sprinkler system:

  • System valve
  • Riser
  • Cross main
  • Branch line

Obstruction Investigation

This is to be performed if foreign organic or inorganic material is found during an internal pipe inspection. NFPA 25 provides the requirements to conduct obstruction investigations.

Allstate Sprinklers Corp. are experts in a NYC sprinkler system inspection. If you have any questions pertaining to commercial fire sprinkler systems, residential fire sprinkler systems, fire system installations, fire system repairs, fire department sprinkler testing, 5 year standpipe test, sprinkler system inspection in NYC, Manhattan, Bronx NY, Brooklyn NY, Queens NY, or Long Island, contact Allstate Sprinklers Corp. at: (718) 597-4060.